PDF- -Epoxy Coa tings Guide - Sherwin-Williams Coatings - Oasis & Oasis LL COAL EFFECT GAS FIRE

LL COAL EFFECT GAS FIRE Installation and Maintenance Instructions Hand these instructions to the use...

Description

Oasis

& Oasis LL COAL EFFECT GAS FIRE Installation and Maintenance Instructions

Hand these instructions to the user

Model No’s KICC00MN,

KICCZZMN,

KICC00SN,

KICCZZSN & KF200N are only for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B.

Model No.

KICC00MP is only for use on Propane Gas (G31) at a supply pressure of 37 mbar in G.B.

Section 1 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9

Assembling Fuel Bed and Commissioning

Assembling the ceramics and fuel bed Lighting the appliance (Manual Control model) Lighting the appliance (Slide Control model) Checking for clearance of combustion products

Section 4

Installation of Fire

Unpacking the fire Installing the fire box Gas tightness and inlet pressure (MC models) Gas tightness and inlet pressure (SC models)

Section 3 3.1 3.2 3.3 3.4

Information and Requirements

Appliance Information Conditions of Installation Flue and chimney suitability Fireplace / surround suitability Shelf position Chimney inspection Fire place opening / catchment space Fitting to Metal Flue Boxes Hearths Spillage Monitoring System

Section 2 2.1 2.2 2.3 2.4

CONTENTS

Maintenance

Removal of the Burner Assembly (Manual) Removal of the Piezo Igniter Removal of the Control Tap Removal of the Pilot Assembly Removal of the Burner Assembly (Slide) Removal of the Battery Ignitor Repacing the Battery Removing the Oxy-Pilot Assembly Replacing the Control Cable

This appliance is manufactured by:BFM Europe Ltd,

Trentham Lakes,

Stoke-on-Trent,

ST4 4TJ 2

SECTION 1 INFORMATION AND REQUIREMENTS 1.0

APPLIANCE INFORMATION

Model Gas Type Main injectors (2 off) Pilot Type Max.

Gross Heat Input : Min.

Gross Heat Input :

KICC00MN (MC) KICCZZMN (MC) KICCZZSN (SC) KF200N G20 Size 260 Copreci 21100 / 141 (MC) 21100 / 162 (SC) 6.9 kW 4.2 kW

KICC00MP (MC) KICC00SP (SC) G31 Size 85 Copreci 21100 / 166 (MC)

Cold Pressure :

KICC00MN,

KICCZZMN,

KICC00SN,

KICCZZSN & KF200N

Ignition :

Push Button Piezo (MC models) 1.5V Battery Generator (SC models)

Electrode Spark Gap

Weight (without fender)

18.0 kg

Fire box Dimensions (with trim fitted) Width : Height : Depth : Depth : Depth :

no spacer) (with standard trim,

no spacer) (overall-without fender) Flush-fit (from mounting face to rear) Flush-fit (mounting face to rear with 50mm spacer fitted)

Gas Connection

Efficiency Declaration The efficiency of this appliance has been measured as specified in BS 7977-1 : 2002 and the result is 58%.

The gross calorific value of the fuel has been used for this efficiency calculation.

The test data from which it has been calculated has been certified by Advantica.

The efficiency value may be used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings.

INSTALLATION REQUIREMENTS 1.1

CONDITIONS OF INSTALLATION

It is the law that all gas appliances are installed only by a Registered Installer,

in accordance with these installation instructions and the Gas Safety (Installation and Use) Regulations 1998 as amended.

Failure to install appliances correctly could lead to prosecution.

It is in your own interest and that of safety to comply with the law.

The installation must also be in accordance with all relevant parts of the Local and National Building Regulations where appropriate,

the Building Regulations (Scotland Consolidation) issued by the Scottish Development Department,

and all applicable requirements of the following British Standard Code of Practice.

BS 5871 Part 3 Installation of Decorative Fuel Effect Gas Fires BS 6891 Installation of Gas Pipework BS 5440 Parts 1 & 2 Installation of Flues and Ventilation BS 1251 Open fire place components BS 715 / BS EN 1856-2 Metal flue pipes for gas appliances BS 6461 Part 1 Installation of Chimneys and flues IS 813 : 1996 Domestic Gas Installation (Republic of Ireland)

No purpose made additional ventilation is normally required for this appliance,

When Installing in I.E.

which is issued by the National Standards Authority of Ireland.

If installing in Northern Ireland,

please consult local building regulations.

Any purpose made ventilation must be checked periodically to ensure that it is free from obstruction.

FLUE AND CHIMNEY SUITABILITY

This appliance is designed for use with conventional brick built or lined chimneys and fabricated flues and metal flue boxes conforming to BS 715 / BS EN 1856-2.

All flues must conform to the following minimum dimensions.

Minimum diameter of circular flues Minimum effective height of all flue types

When fitting to conventional chimneys or 175mm flues it may be desirable to fit the flue restrictor baffle (supplied) to reduce the flue flow and increase the efficiency of the fire.

Safe clearance of products must always be checked by carrying out a smoke match test as described.

FIREPLACE / SURROUND SUITABILITY

The fire must only be installed on a hearth it must not be installed directly onto carpet or other combustible floor materials.

The fire is suitable for fitting to non-combustible fire place surrounds and proprietary fire place surrounds with a temperature rating of at least 150oc.

If a heating appliance is fitted directly against a wall without the use of a fire surround or fire place all combustible material must be removed from behind the trim.

Soft wall coverings such as blown vinyl,

could be affected by the rising hot air and scorching and/or discoloration may result.

Due consideration should be made to this when installing or decorating.

SHELF POSITION

The fire may be fitted below a combustible shelf providing there is a minimum distance of 200mm above the top of the fire and the shelf does not project more than 150mm.

If the shelf overhangs more than 150mm the distance between the fire and the shelf must be increased by 15mm for every 25mm of additional overhang over 150mm.

FLUE / CHIMNEY INSPECTION

Before commencing installation,

a flue or chimney should be inspected to ensure that all the following conditions are satisfied.

Check that the chimney / flue only serves one fire place and is clear of any obstruction.

Any dampers or register plates must be removed or locked in the open position.

Brick/stone built chimneys or any chimney or flue which has been used for an appliance burning fuel other than gas must be thoroughly swept.

The base of the chimney / flue must also be thoroughly cleared of debris etc.

Any under-floor air supply to the fire place must be completely sealed off.

Ensure that the inside of the chimney / flue is in good condition along it’s length and check that there is no leakage of smoke through the structure of the chimney during and after the smoke pellet test.

With pre-cast flues it is especially important to check the inside of the flue for extruded cement / sealant protruding from the joints between the flue blocks.

If present,

these should be removed by rodding the flue before proceeding with the installation.

Using a smoke pellet,

check that there is an up-draught in the chimney / flue and that the smoke can be seen issuing from the terminal / chimney pot outside.

There must be no leakage of smoke through the structure of the chimney during or after the smoke pellet test and it is important to check inside upstairs rooms adjacent to the chimney / flue.

Check the chimney pot / terminal and general condition of the brickwork or masonry.

If the chimney or flue is in poor condition or if there is no up-draught do not proceed with the installation.

If there is a history of down-draught conditions with the chimney / flue,

a tested and certificated flue terminal or cowl suitable for the relevant flue type should be considered.

A spillage test must always be carried out during commissioning of the appliance.

FIRE PLACE OPENING AND CHIMNEY CATCHMENT SPACE

The front opening of the fire place must be between 400 and 450 mm wide,

and between 550 and 570mm high,

or 500mm to 510mm for low lintle models.

If the opening exceeds these dimensions then a surround must be constructed from suitable non-combustible material to produce a correct size opening.

Any surround must be suitably sealed to the fire place to prevent leakage.

See below in fig.1 Fig.

Minimum Flat Sealing Area

When installing into a brick built chimney,

you must ensure that there is sufficient depth to accomodate any debris which may fall from the chimney.

This depth must be sufficient to accomodate 12 litres of volumetric space.

Table A

requiring 12.0 litres of debris collection volume (fig.

Minimum Depth Required (mm)

For example,

if the appliance was to be fitted into a 400mm wide opening,

the depth required would be 298mm.

See fig.

Depth Required (e.g.

Opening Width ( e.g.

400mm)

(for example the Selkirk LFE 175 box).

The box must have a minimum flue diameter of 175mm internal and minimum internal dimensions of 300mm deep by 580mm high by 400mm wide.

There are no maximum dimensional requirements for the box.

The top face of the box must be insulated with a minimum thickness of 50mm of non-combustible mineral wool insulation or similar material.

The flue box must stand on a non-combustible base of minimum thickness 12mm.

HEARTHS

This appliance must only be installed on to a concrete or non-combustible hearth.

The hearth material must be a minimum thickness of 13mm with the top surface at least 50mm above the floor.

The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760mm and a minimum projection of 300mm forwards from the fire opening.

If the appliance is fitted with a black 50mm spacer frame,

then the hearth projection must be increased to 350mm forwards of the fireplace opening.

SPILLAGE MONITORING SYSTEM

This appliance is fitted with an atmosphere sensing spillage monitoring system in the form of an oxygen sensing pilot.

This is designed to shut the fire off in the event of a partial or complete blockage of the flue causing a build up of combustion products in the room in which the fire is operated.

The following are important warnings relating to this spillage monitoring system :1) The spillage monitoring system must not be adjusted by the installer.

It is not possible to replace individual parts on the pilot system on this appliance,

only a complete pilot assembly (including the thermocouple) may be fitted.

SECTION 2 INSTALLATION OF FIRE 2.1

UNPACKING THE FIRE

Carefully lift the fire out of the carton.

Remove the loose item packaging carefully from the front of the appliance.

Check the contents as listed :Packing Check List 1off 1off

Fire box / burner assembly Boxed ceramic base,

front ceramic rail and 20 coals (18 large,

INSTALLING THE FIRE BOX

Establish which type of flue you are intending to install the fire in to :225 x 225mm (9 inch x 9 inch) brick built chimneys 175mm (7 inch) diameter lined brick or stone flue,

insulated pre-fabricated metal flue box to BS 715 / BS EN 1856-2.

When installing into 125mm (5 inch) diameter lined brick or stone flue,

or insulated pre-fabricated metal flue box and liner to BS 715 / BS EN 1856-2 the restrictor baffle must be removed.

A spillage test must always be carried out to check satisfactory clearance of flue products,

regardless of the type of flue the appliance is being fitted to.

For manual control models proceed as follows :a)

Remove the trim / fret.

Remove the burner heat shield from the front of the fire box to allow access to the burner.

See fig.

3 below.

Ensure that the hearth is protected from damage and carefully lift the fire box into the fire opening,

then slide it back into position.

Check that the fire box flange fits flush to the sealing face of the fire surround or wall with no gaps present.

Remove the four retaining screws securing the burner to the firebox.

The base of the burner unit can now be pulled forward,

allowing the burner to be removed outwards and downwards from the fire box.

See fig.

4 below.

For Slide Control Models Proceed as follows: d) Fig.

Remove the trim / fret.

Remove the burner heat shield from the front of the fire box to allow access to the burner.

See fig.

5 below.

Ensure that the hearth is protected from damage and carefully lift the fire box into the fire opening,

then slide it back into position.

Check that the fire box flange fits flush to the sealing face of the fire surround or wall with no gaps present.

Remove the burner.

To allow burner removal,

the control lever operat ing cable must be removed.

The control lever operating cable can be seen running across the base of the fire,

To release the cable,

unscrew the cable securing screw located in the centre of the aluminium operating arm and pull the cable out from its fixing hole.

Release the other end of the cable by pushing the cable forwards to the right,

into the operating arm so as to release the tension.

Pull the cable nipple out of the retaining hole and remove the cable through the slot in the operating arm.

See fig.

6 overpage

Unscrew the burner assembly fixing screws at either side of the firebox,

and the two fixing screws at the base of the fire (See fig.

6 above).

Carefully pull the base of the burner forwards and downwards from the fuel-bed support panel.

The burner can now be removed from the appliance.

Continue for all models Whilst the fire box is still in position,

decide which side the gas supply is to enter the fire from.

If concealed pipe work is required plan the pipe run to enter the fire box through one of the openings in the sides of the fire box below the fuelbed support panel and connect to the isolating / inlet elbow.

The gas connection to the appliance should be made to the isolating / inlet elbow using 8mm rigid tubing.

There must be no soldered joints within the firebox.

See fig.

Gas Supply

Firebox

Approx.

Fireplace

Gas Supply

Builders Opening

Firebox

Approx.

Fireplace

Note : Before breaking into the gas supply a pressure drop test should be carried out to establish that the existing pipework is sound.

Carefully withdraw the fire box from the opening to enable the gas supply and fire fixing to be completed.

IMPORTANT : Sealing of the Gas Unused Gas Pipe Inlet Apertures In line with current regulations,

it is imperative that the gas supply inlet apertures that are not utilised during the installation are sealed with the foil tape as supplied.

Failure to seal these inlet apertures could lead to flame reversal,

which in turn will damage the burner and control systems of the product.

Seal off unused gas inlet apertures and cable fixing holes as shown

PLEASE NOTE :BFM EUROPE LTD.

WILL NOT BE LIABLE FOR GUARANTEE CLAIMS THAT ARE AS A DIRECT RESULT OF THE UNUSED GAS INLET APERTURES NOT BEING CORRECTLY SEALED.

The preferred method of fixing which is suitable for almost all situations is the cable fixing method which is described in the following section in detail.

If the 2 inch black spacer is used,

the fire may be secured using the cable method as described below,

in installations where the cable method is not suitable (eg.

loose masonary in rear of fire opening) the spacer may be removed from the fire box and secured to the fire surround using protruding screws which engage on to the key hole slots on the rear face of the spacer.

The spacer will then need to be sealed to the fire surround.

The fire box can then be refitted to the spacer.

To fit using the preferred cable method proceed as followsh)

Mark out and drill 4 off No 14 (6mm) holes in the back face of the fire opening in the positions shown below in fig.

100mm

Fireplace Opening 20mm

Fit the wallplugs provided and screw the fixing eyes securely into the rear of the fire opening.

If the clearance at the rear of the fire is at the minimum specified for a precast flue application,

it may be necessary to bend over the lower fixing eyes after screwing them fully in to the rear of a pre-cast starter block.

Uncoil the two fire fixing cables and thread one end of each of the cables through one of the two holes on each side of the flue outlet shroud.

Position the fire carefully on the (protected) surface of the hearth and reach into the fire opening.

Thread each of the cables vertically downwards through the pair of fixing eyes on the same side of the fire.

Thread the free end of the cables through the corresponding circular hole on each side of the lower rear of the fire.

Carefully slide the fire box back into the fire opening and pull both cables tight.

Thread a tensioning screw over each of the cables and ensure that the tensioning nut is screwed fully up against the hexagon shoulder of the tensioning screw (this provides maximum travel for the tensioning nut).

Fit a screwed nipple on to each of the cables and pull hand tight up against the tensioning screw,

then secure each nipple with a flat bladed screwdriver.

See fig.

11 below

Evenly tighten the tensioning nuts to tension both cables and pull the fire snugly against the wall.

Do not overtighten,

it is only necessary to pull the seal up against the sealing face of the wall,

it does not need to be compressed.

Check that there are no gaps behind the seal.

With the fire securely in place,

if a concealed gas connection has been made through either of the access holes in the sides of the fire,

the holes should be closed around the pipe to prevent leakage of air through the gap around the pipe.

Refit the burner.

Fit the four retaining screws and check that the burner is correctly locked into position.

On slide control models refit the control cable To do this,

firstly locate the nipple on one end of the cable into recess in operating arm and then secure the front part of the operating arm back onto the rear of the operating arm with the retained screw.

This should not be overtightened.

Move the control lever fully downwards and check that the left hand micro-switch operates the igniter and that the control valve spindle is fully depressed.

Move the control lever upwards to the “off” position and check that the right hand (cut-off) micro-switch operates.

Check that the control lever operates smoothly and safely.

NOTE : The cable is factory set,

and therefore should need no adjustment p)

Refit the front burner heat shield to the sides of the fire box (2 Screws) and secure the trim to the fire using the magnets provided.

Before making the final gas connection,

thoroughly purge the gas supply pipework to remove all foreign matter,

otherwise serious damage may be caused to the gas control valve on the fire.

The other firebox fixing method is as follows :In installations where the cable method is not suitable (e.g.

loose masonary in rear of fire opening) the firebox can be secured to the fire surround using four screws and wall plugs provided.

Below (fig.12) is a diagram to indicate the hole centre positions available on the firebox to facilitate the screw fixing to the fireplace / surround.

260mm

Firebox Mounting Flange

532mm 37mm

425mm

GAS TIGHTNESS AND INLET PRESSURE (MANUAL CONTROL MODELS)

Remove the pressure test point screw from the inlet elbow and fit a manometer.

Turn on the main gas supply and carry out a gas tightness test.

Depress the control knob and turn anti-clockwise to the position marked pilot.

Hold in the control knob for a few seconds to purge the pipe work then press the igniter button.

The burner should light,

continue to hold the control knob for a few seconds then turn to the full-on position.

Check that the gas pressure for Natural Gas (G20) models is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/- 0.4 in w.g.) or for LPG models 37.0 mbar (+/- 1.0mbar) 14.8 in w.g.(+/- 0.4 in w.g.)

Turn off the fire,

remove the manometer and refit the pressure test point screw.

Check the pressure test point screw for gas tightness with the appliance turned on using a suitable leak detection fluid or detector.

GAS TIGHTNESS AND INLET PRESSURE (SLIDE CONTROL MODELS).

Remove the pressure test point screw from the pressure test point and fit a manometer.

Turn on the main gas supply and carry out a gas tightness test.

Depress the control lever to the position marked pilot.

Hold down the control lever for a few seconds to purge the pipe work.

The burner should light,

continue to hold the control lever for a few seconds to latch the valve then lift to the full-on position.

Check that the gas pressure for Natural Gas (G20) models is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/- 0.4 in w.g.) or for LPG models 37.0 mbar (+/- 1.0mbar) 14.8 in w.g.(+/- 0.4 in w.g.)

Turn off the fire,

remove the manometer and refit the pressure test point screw.

Check the pressure test point screw for gas tightness with the appliance turned on using a suitable leak detection fluid or detector.

SECTION 3 ASSEMBLING FUEL BED AND COMMISSIONING 3.1

ASSEMBLING THE CERAMICS AND FUEL BED

Place the ribbed ceramic fuelbed base on top of the fuelbed support and pull fully forwards to the burner.

Make sure that the fuelbed base is located centrally in the fire box.

Ensure that the fuelbed base fit fully down onto the fuel bed support and is not lodged on the burner.

See fig.

13 below.

NOTE : The position of the fuel-bed components are critical to the performance of the product.

Therefore please ensure that the fuel-bed components are positioned as described in the following section prior to requesting a service call due to soot build up,

Position the two halves of the front ceramic (L/H & R/H) on the locating channel in the front ceramic,

ensuring it is located onto the lip on the burner front ceramic support.

(See fig.

14 below)

Fit five of the large sized coals onto the front ceramic rail,

ensuring that they are evenly spaced.

Use the recess’s in the front ceramic rail as a guide for placement.

(See fig.

15 below)

Select four of the large coals and arrange behind the front row of coals,

ensuring that flame paths as indicated below are not interupted.

Select two of the small coals and place at each end of the second row (See fig.

16 below)

Select five of the large coals and arrange along the rear of the fuelbed,

using the ribs in the rear of the fuelbed as a guide for placement.

(See fig.

17 below)

Select the four remaining large coals and position to fill the gaps at the rear of the fuel-bed,

The exact position and fit of the coals may be finely adjusted to give the most pleasing and random appearance.

Warning : Use only the coals supplied with the fire.

When replacing the coals remove the old coals and discard them.

Fit a complete set of coals of the correct type.

Do not fit additional coals or any coals other than a genuine replacement set.

To ensure that the release of fibres from these R.C.F (Refractory Ceramic Fibre) articles is kept to a minimum,

during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust accumulated in and around the appliance before and after working on the appliance.

When replacing these articles we recommend that the replaced items are not broken up,

but are sealed within heavy duty polythene bags,

clearly labelled as “RCF waste”.

RCF waste is classed as a “stable”,

non reactive hazardous waste and may be disposed of at a landfill licensed to accept such waste Protective clothing is not required when handling these articles,

but we recommend you follow the normal hygiene rules of not smoking,

eating or drinking in the work area,

and always wash your hands before eating or drinking.

LIGHTING THE APPLIANCE (Manual Control Models)

Turn on the gas isolation tap.

Depress the control knob and turn anti-clockwise to the position marked pilot.

Hold in the control knob for a few seconds to purge the pipe work.

Continue to hold-in the control knob and press the igniter button.

If the burner does not light,

continue to press the igniter button until ignition occurs.

Continue to hold the control knob for 5-10 seconds to allow the thermocouple to heat up,

if the pilot goes out when the control knob is released,

Turn the control knob in the anti-clockwise direction to the high position and the main burner will light.

Turn the control knob clockwise to the low position and the gas input will be reduced to the minimum setting.

Slightly depress the control knob and turn to the pilot position,

the main burner will go out but the pilot will remain lit.

Slightly depress the control knob and turn to the off position,

the pilot will now be extinguished.

LIGHTING THE APPLIANCE (Slide Control Models)

Turn on the isolation valve.

Depress the control lever fully downwards to the position marked.

Hold down the control lever for a few seconds to allow the gas to reach the pilot.

The fire will then begin its ignition sequence.

If the pilot does not light,

continue to press the control lever until ignition occurs.

The pilot flame can be seen by looking underneath the front ceramic rail,

at the front left hand side of the fuel.

When the pilot has lit,

continue to hold the control lever down for 5-10 seconds to allow the thermocouple to heat up,

before releasing the lever apply one firm downwards push to ensure that the f.s.d.

if the pilot goes out when the control lever is released,

After lighting,

move control lever up to the high position and the main burner will light.

It is recommended that for the most efficient performance the fire is allowed to warm up for a few minutes with the flame adjuster set to the left hand position and the control lever set to high.

The gas control can be moved from the High to Low position to give the desired heat output and the flame control adjusted to give the most pleasing flame effect or maximum glow.

To turn the fire off,

FULLY raise the control lever to the OFF position.

CHECKING FOR CLEARANCE OF COMBUSTION PRODUCTS

Close all doors and windows in the room.

Light the fire and allow to run for approximately 5 minutes on high position.

After approximately 5 minutes hold a smoke match just inside and below the centre of the lower front edge of the top of the fire.

(It is recommended that a suitable smoke match holder is used when check ing for clearance of combustion products).

All smoke generated should be drawn back into the flue.

If slight spillage occurs or if in doubt,

repeat the test after a further 5-10 minutes.

If the test indicates that spillage is occurring and the flue restrictor baffle has been fitted,

it should be removed and the test repeated after the fire has cooled.

If spillage persists,

the flue is not functioning correctly and a fault exists.

after investigation the fault cannot be traced and rectified,

the fire must be disconnected from the gas supply and expert advice obtained.

If there is an extractor fan fitted any where in the vicinity of the appliance,

the spillage test should be repeated with the fan running on maximum and all interconnecting doors open.

After ensuring that the fire is safe to use it should be left on high position to fully warm up.

During this time a slight odour may be noticed,

this is due to the “newness” of the fire and will soon disappear.

WARNING : If the fire goes out for any reason or is turned off and it isnecessary to re-light the fire it is important to allow the fire to cool for 3 minutes before attempting to re-light it.

At this stage any minor adjustments to the coals should be made using suitable long handled tongs and taking care not to damage the coals.

Finally,

hand the Installation and Maintenance Instructions and the Users Instructions over to the customer and explain the operation of the fire.

SECTION 4 MAINTENANCE Servicing Notes Servicing shoul

OASIS RESIDENCE YÖNETİM PLANI

Değerleme Konusu Gayrimenkullerin - nurolgyocom

nurolgyo upi r nurol gayrimenkul yatirim Şirketimizin Yönetim Kurulu Üyeleri üç yıl süreyle görev yapmak üzere Ortaklar Genel Kurul , “OASİS Designer Outlet”e ev Nurol Residence nihai

OAXACA DEL 3 AL 9 DE MAYO

The Unbroken Thread: Conserving the Textile Traditions of Oaxaca

Mar 21, 2017 in Mexico's Valley of Oaxaca, the Zapotec heartland (Fig 1) This paper A series of radiocarbon dates indicates that the El sue a death sentence (9) El Palenque is one of three archaeological sites near San

OB Dieter Salomon: Habemus Haushalt

Hamburgs Gedächtnis - die Threse des Hamburger Rates Die

EVELYN ADUNKA Salomon Frankfurter (1856–1941) Amt antritt und Klaus Dieter Lehmann, von Haus aus Bibliothekar, ablöst, mag als vorgesehenen Haushalt zum Zweck einer Vorort Selektierung der kostbarsten Ob das jetzt in Marburg aufgefundene Buch aus dem »Posten Bücher«

ระบบงานสาน กงานอ เล กทรอน กส (OBEC e-office) ระบบพ สด (ว สด -คร ภ ณฑ )

obejmujące informacje dotyczące działalności jednostki dominującej i Grupy Kapitałowej za okres od 1 stycznia 2011 roku do 31 grudnia 2011 roku

code of conduct - Sumitomo Electric Industries, Ltd

PDF Zakres tematyczny poszczególnych działów „Wiadomości stat gov pl ws 02 2019 10 zakres tematyczny poszczegolnych dzialow wiadomosci statystycznych the polish statistaci pdf PDF Akt prawny Internetowy System Aktów Prawnychprawo sejm gov pl isap nsf download xsp

Obergericht Appenzell Ausserrhoden 3. Abteilung

Übermässige Bindung im Aktionärbindungsvertrag - UZH

Die Einzelrichter des Obergerichts hatten im Bereich Zivil und Straf halbe Tage 1 Abteilung 1 (2) 11 ( 5) 2 Abteilung 0 (0) 7 (10) 3 Abteilung 0 (0) 13 Dez

OBERHAU AKTUELL E. V. Verein zur Förderung der Heimatpflege. Monatlich kostenlos. Ausgabe März 2016

magisterarbeit-DIN a5 - aktuell - Toni Schuberl

3 Febr 2019 OBERHAU AKTUELL E V Verein zur Förderung der Heimatpflege Monatlich · kostenlos Ausgabe Februar 2019 20 Jahre Jugendorchester  17 Nov 2017 Verein Agrar Informator Pfaffenwinkel e V

Oberhirtliches Verordnungsblatt

Datenschutzerklärung des Bischöflichen Priesterseminars St

21 Febr 2018 Oberhirtliches Verordnungsblatt Amtsblatt für das Bistum Speyer Herausgegeben und verlegt vom Bischöflichen Ordinariat Speyer 1 Juli 2017 Oberhirtliches Verordnungsblatt Amtsblatt für das Bistum Speyer Herausgegeben und verlegt vom Bischöflichen Ordinariat Speyer Oberhirtliches

Oberhirtliches Verordnungsblatt

Domkapitular Offizial Prälat Dr Josef Ammer

bistum speyer de fileadmin user upload 1 0 0 Oberhirtliches Verordnungsblatt AmtsblattfürdasBistumSpeyer HerausgegebenundverlegtvomBischöflichenOrdinariatSpeyer INHALT 110 Jahrgang Nr 4 21 Juni2017 pfarrei bobenheim roxheim de fileadmin user Verpflichtungserklärung Ehrenamtliche Stand Januar 2019 Verpflichtungserklärung für Ehrenamtliche in der Pfarrei Hl Petrus Bobenheim Roxheim kath datenschutzzentrum ffm de

Home back Next

Kinder Oasis Gas Fire Manual - WordPresscom

skulsourrome files wordpress 2015 08 kinder The open fronted Kinder Oasis Low Lintel Gas Fire is operated via Manual control and is suitable for use with Natural Gas only Oasis HE COAL EFFECT HIGH EFFICIENCY GAS FIRE Installation, Maintenance & User Instructions Hand these instructions to the owner following There is nothing like the immediate warmth and comfort of a Kinder Gas fire

https://skulsourrome.files.wordpress.com/2015/08/kinder-oasis-gas-fire-manual.pdf

Coal Effect Gas Fire Manual - trafexovinfileswordpresscom

trafexovin files wordpress 2015 09 coal For sale Strax coal effect gas fire (plus instructions) Good working order Just removed from lounge Collection from Markfield LE67 area For viewing further Gas Hearth Mounted Fires, Log & Coal Effect Gas Fires Online, Flueless The Flavel Waverley comes in natural gas and manual control only and comes Oasis COAL EFFECT GAS FIRE

https://trafexovin.files.wordpress.com/2015/09/coal-effect-gas-fire-manual.pdf

Maryland Contract Summary - Spark Energy - Natural Gas

sparkenergy Document pdf TOS TOS 139696 pdf biomass Oasis Energy does not own any coal, oil, gas, or nuclear generation facilities We are not the subsidiary of any company that owns coal, oil, gas or nuclear generation facilities 100 CARBON OFF SET GAS PLAN (FIXED TERM) For our carbon off set natural gas products, Oasis Energy will offset

https://www.sparkenergy.com/Document/pdf/TOS/TOS_139696.pdf

CLICK TO EDIT MASTER TITLE STYLE 2018 Fall - oasisoaticom

oasis oati woa docs ITCM ITCMdocs 2018 conversion to natural gas, before closing it in 2016 • Closings planned for three other plants in Cassville, Wisconsin, and Clinton, Iowa • To address the issues, ITC • built Dubuque 8th Street Salem 161 kV line, • constructed the Hickory Creek substation, • rebuilt the Hickory Creek Lore line • moved ahead with plans for the Cardinal

https://www.oasis.oati.com/woa/docs/ITCM/ITCMdocs/2018_Fall_PIB_South_Presentation_final_for_Oasis_10.09.18.pdf

Recommended Reading on Energy - Reuters News Agency

fingfx thomsonreuters gfx ce 4 712 711 RECOMMENDED Recommended Reading on Energy John Kemp Reuters (A) Energy systems Latin America oil and gas (LL) Oil spills and pollution The Oasis of Al Hasa (Vidal Aramco

https://fingfx.thomsonreuters.com/gfx/ce/4/712/711/RECOMMENDED%20READING%20ON%20ENERGY.pdf

Manual Control Gas Fire Baskets - WordPresscom

inulbarro files wordpress 2015 07 manual it on its coal effect gas or electric fire or burning logs and coal with the solid fuel kit option Manual control with on off and flame height adjustment operated Burners for Fireplace Inserts Complete your fireplace insert with a natural gas or propane gas Hargrove Faux Wood Vented Natural Gas Burner with Manual

https://inulbarro.files.wordpress.com/2015/07/manual-control-gas-fire-baskets.pdf

<